SAF Fixed RPM Series
Indoor Units Outdoor Units
SAF024 OU7-24Z
SAF045
OU10-47T
GC 45
AUGUST 2009
REFRIGERANT
R22
HEAT PUMP
COOLING ONLY
R410A
SM SAFRPM 1-A.0 GB
CONTENTS
Przeglądanie stron 0
1 2 3 4 5 6 ... 54 55

Podsumowanie treści

Strona 1 - SAF Fixed RPM Series

SAF Fixed RPM SeriesIndoor Units Outdoor UnitsSAF024 OU7-24ZSAF045OU10-47TGC 45AUGUST 2009REFRIGERANTR22HEAT PUMPCOOLING ONLYR410ASM SAFRPM 1-A.0 GBC

Strona 2 - LIST OF EFFECTIVE PAGES

OUTLINE DIMENSIONS4-1SM SAFRPM 1-A.0 GB4. OUTLINE DIMENSIONS4.1 Indoor Unit: SAF024, SAF0454.2 Outdoor Unit: OU7-24Z R410ABACModel A B CSAF024 485 m

Strona 3 - Table of Contents

OUTLINE DIMENSIONS4-2SM SAFRPM 1-A.0 GB4.3 Outdoor Unit: OU10-47T R410A4.4 Outdoor Unit: GC 45 R22127095011 2 . 565.4378187.557234080.881CONTENTS

Strona 4 - 1. INTRODUCTION

PERFORMANCE DATA & PRESSURE CURVES5-1SM SAFRPM 1-A.0 GB5. PERFORMANCE DATA5.1 SAF024 / OU7-24 Z R410A5.1.1 Cooling Mode at 7.5m Tubing Connectio

Strona 5 - INTRODUCTION

PERFORMANCE DATA & PRESSURE CURVES5-2SM SAFRPM 1-A.0 GB5.1.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed.ENTERING AI

Strona 6 - 2. PRODUCT DATA SHEET

PERFORMANCE DATA & PRESSURE CURVES5-3SM SAFRPM 1-A.0 GB5.2 SAF045 / OU10-47T R410A5.2.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor F

Strona 7 - 2.2 SAF045 / OU10-47T R410A

PERFORMANCE DATA & PRESSURE CURVES5-4SM SAFRPM 1-A.0 GB5.2.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed.ENTERING AI

Strona 8 - 2.3 SAF045 / GC 45 R22

PERFORMANCE DATA & PRESSURE CURVES5-5SM SAFRPM 1-A.0 GB5.3 SAF045 / GC 45 R225.3.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at

Strona 9 - 3. RATING CONDITIONS

PERFORMANCE DATA & PRESSURE CURVES5-6SM SAFRPM 1-A.0 GB5.3.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed.ENTERING A

Strona 10 - 4. OUTLINE DIMENSIONS

PERFORMANCE DATA & PRESSURE CURVES5-7SM SAFRPM 1-A.0 GB5.4 Pressure Curves: SAF024 / OU7-24 Z R410A5.4.1 Cooling.Discharge Pressure VS.Outdoor Te

Strona 11 - 11 2 . 5

PERFORMANCE DATA & PRESSURE CURVES5-8SM SAFRPM 1-A.0 GB5.4.2 Heating.Discharge Pressure VS.Outdoor Temp16182022242628303234363840-10-5 0 5 101520O

Strona 12 - 5. PERFORMANCE DATA

LIST OF EFFECTIVE PAGESA SM SAFRPM 1-A.0 GB LIST OF EFFECTIVE PAGESNote: Changes in the pages are indicated by a “Revision#” in the footer of each e

Strona 13

PERFORMANCE DATA & PRESSURE CURVES5-9SM SAFRPM 1-A.0 GB5.5 Pressure Curves: SAF045 / OU10-47T R410A5.5.1 Cooling.Discharge Pressure VS.Outdoor Te

Strona 14 - 5.2 SAF045 / OU10-47T R410A

PERFORMANCE DATA & PRESSURE CURVES5-10SM SAFRPM 1-A.0 GB5.5.2 Heating.Discharge Pressure VS.Outdoor Temp16182022242628303234363840-10-5 0 5 101520

Strona 15

PERFORMANCE DATA & PRESSURE CURVES5-11SM SAFRPM 1-A.0 GB5.6 Pressure Curves: SAF045 / GC 45 R225.6.1 Cooling.Discharge Pressure VS.Outdoor Temp81

Strona 16 - 5.3 SAF045 / GC 45 R22

PERFORMANCE DATA & PRESSURE CURVES5-12SM SAFRPM 1-A.0 GB5.6.2 Heating.Discharge Pressure VS.Outdoor Temp12141618202224-10 -5 0 5 10 15 20Outdoor T

Strona 17

6-1SOUND LEVEL CHARACTERISTICSSM SAFRPM 1-A.0 GB6. SOUND LEVEL CHARACTERISTICS6.1 Sound Pressure Level6.2 Sound Pressure Level Spectrum (Measured a

Strona 18 - CONTENTS

6-2SOUND LEVEL CHARACTERISTICS SM SAFRPM 1-A.0 GB6.3 Outdoor units6.4 Sound Pressure Level Spectrum (Measured as Figure 2)OU7-24 Z Cooling OU7

Strona 19 - 5.4.2 Heating

WIRING DIAGRAMS7-1SM SAFRPM 1-A.0 GB7. WIRING DIAGRAMS7.1 Indoor Units: SAF024, SAF045CONTENTS

Strona 20 - 5.5.1 Cooling

WIRING DIAGRAMS7-2SM SAFRPM 1-A.0 GB7.2 Indoor Unit: OU7-24 Z R410ACONTENTS

Strona 21 - 5.5.2 Heating

WIRING DIAGRAMS7-3SM SAFRPM 1-A.0 GB7.3 Indoor Unit: OU10-47T R410ACONTENTS

Strona 22 - 15 20 25 30 35 40 46

WIRING DIAGRAMS7-4SM SAFRPM 1-A.0 GB7.4 Outdoor Unit: GC 45 R22CONTENTS

Strona 23 - 5.6.2 Heating

TABLE OF CONTENTSiSM SAFRPM 1-A.0 GBTable of Contents1. INTRODUCTION ...

Strona 24 - SOUND LEVEL CHARACTERISTICS

WIRING DIAGRAMS7-5SM SAFRPM 1-A.0 GB7.5 Connections between indoor unit and outdoor unitNote: 1. ─ ─ ─ ─ Connection only for heat pump model2.

Strona 25 - Figure 2

8-1ELECTRICAL DATASM SAFRPM 1-A.0 GB8. ELECTRICAL DATA8.1 SAF024, SAF045Note: Power wiring cord should comply with local laws and electrical regulati

Strona 26 - 7. WIRING DIAGRAMS

REFRIGERATION DIAGRAMS9-1SM SAFRPM 1-A.0 GB9. REFRIGERATION DIAGRAMS9.1 SAF024 / OU7-24Z R410AStrainerStrainervalveCheckCapillarytubeCapillarytubetub

Strona 27 - WIRING DIAGRAMS

REGRIGERATION DIAGRAMS9-2SM SAFRPM 1-A.0 GB9.2 SAF045 / OU10-47T R410ACONTENTS

Strona 28

REFRIGERATION DIAGRAMS9-3SM SAFRPM 1-A.0 GB9.3 SAF045 / GC 45 R22CONTENTS

Strona 29 - 7.4 Outdoor Unit: GC 45 R22

10-1TUBING CONNECTIONSSM SAFRPM 1-A.0 GB10. TUBING CONNECTIONS TUBE (Inch)TORQUE (Nm)¼” ⅜”½”⅝”¾”Flare Nuts 11-13 40-45 60-65 70-75 80-85Valve Cap

Strona 30

CONTROL SYSTEM11-1SM SAFRPM 1-A.0 GB11. CONTROL SYSTEM11.1 SAFETY CONTROL11.1.1 Time delay safety controla. 3 minutes delay for compressor—the compre

Strona 31 - 8. ELECTRICAL DATA

CONTROL SYSTEM11-2SM SAFRPM 1-A.0 GB11.4 “DRY” Mode Operation1.4.1 The system for DRY operation used the same refrigerant circle as the cooling circ

Strona 32 - 9. REFRIGERATION DIAGRAMS

CONTROL SYSTEM11-3SM SAFRPM 1-A.0 GB11.5.5 DefrostDefrosting of the outdoor heat exchange is controlled by the microprocessor with detection by the in

Strona 33 - 9.2 SAF045 / OU10-47T R410A

CONTROL SYSTEM11-4SM SAFRPM 1-A.0 GBB. After the compressor cumulative operation time exceeds 120 minutes and the temperature of the IPT is less then

Strona 34 - 9.3 SAF045 / GC 45 R22

1-1INTRODUCTIONSM SAFRPM 1-A.0 GB1. INTRODUCTION1.1 GeneralThe floor-standing air conditioner of SAF fixed RPM series has some strongpoint, such as mo

Strona 35 - ¼” ⅜”½”⅝”¾”

CONTROL SYSTEM11-5SM SAFRPM 1-A.0 GB11.8 “SLEEP” modeWhen the SLEEP button is pressed, the SLEEP mode is selected as following:1. The indoor fan speed

Strona 36 - 11. CONTROL SYSTEM

CONTROL SYSTEM11-6SM SAFRPM 1-A.0 GB11.11.2 PositioningThe vane is once pressed to the cane stopper below to confirm the standard position and then se

Strona 37 - 11.4 “DRY” Mode Operation

CONTROL SYSTEM11-7SM SAFRPM 1-A.0 GBThe thermostat is ON and timer is reset to normal.After 30 minutes of test run operation the system shifts to AUTO

Strona 38 - 11.5.5 Defrost

CONTROL SYSTEM11-8SM SAFRPM 1-A.0 GB11.16.4 Display of the controlIn the display board the lamp from left is the POWER lamp (Red), the SLEEP lamp (Ye

Strona 39 - 11.7 4-way valve control

12-1TROUBLESHOOTINGSM SAFRPM 1-A.0 GB12. TROUBLESHOOTINGTrouble AnalysisDoes not runNot cool or warmenoughIneffective controlDoes not operate

Strona 40 - 11.10 Auto fan speed control

EXPLODED VIEWS & SPARE PARTS LISTS13-1SM SAFRPM 1-A.0 GB13. EXPLODED VIEWS & SPARE PARTS LISTS13.1 Indoor Unit: SAF024CONTENTS

Strona 41 - 11.13 Emergency Operation

EXPLODED VIEWS & SPARE PARTS LISTS13-2SM SAFRPM 1-A.0 GB13.2 Indoor Unit: SAF024No. Items Description Quantity 1 1070710042 Inside Base 12 1210

Strona 42 - 11.15 Electron lock function

EXPLODED VIEWS & SPARE PARTS LISTS13-3SM SAFRPM 1-A.0 GB13.3 Indoor Unit: SAF045CONTENTS

Strona 43 - CONTROL SYSTEM

EXPLODED VIEWS & SPARE PARTS LISTS13-4SM SAFRPM 1-A.0 GB13.4 Indoor Unit: SAF045 No. Items Description Quantity 1 1301200262 Inside

Strona 44 - 12. TROUBLESHOOTING

EXPLODED VIEWS & SPARE PARTS LISTS13-5SM SAFRPM 1-A.0 GB13.5 Outdoor Unit: OU7-24 Z2019a18172444*OptionalCONTENTS

Strona 45 - 13.1 Indoor Unit: SAF024

1-2INTRODUCTIONSM SAFRPM 1-A.0 GBIndoor UnitOutdoor Unit1.6 Tubing ConnectionsFlare type interconnecting tubing to be produced on site.For further det

Strona 46 - 13.2 Indoor Unit: SAF024

EXPLODED VIEWS & SPARE PARTS LISTS13-6SM SAFRPM 1-A.0 GB13.6 Outdoor Unit: OU7-24 ZNo. Item Description Quant1 437045 LARGE UPPER COVER CUE 12 4

Strona 47 - 13.3 Indoor Unit: SAF045

EXPLODED VIEWS & SPARE PARTS LISTS13-7SM SAFRPM 1-A.0 GB13.7 Outdoor Unit: OU10-47TCONTENTS

Strona 48 - 13.4 Indoor Unit: SAF045

EXPLODED VIEWS & SPARE PARTS LISTS13-8SM SAFRPM 1-A.0 GB13.8 Outdoor Unit: OU10-47T SP No. Item Description Quantity1 437045 UPPER COVER EL13 OU

Strona 49 - 13.5 Outdoor Unit: OU7-24 Z

EXPLODED VIEWS & SPARE PARTS LISTS13-9SM SAFRPM 1-A.0 GB13.9 Outdoor Unit: GC 45 R22CONTENTS

Strona 50 - 13.6 Outdoor Unit: OU7-24 Z

EXPLODED VIEWS & SPARE PARTS LISTS13-10SM SAFRPM 1-A.0 GB13.10 Outdoor Unit: GC 45 R22No. Part No. Description Quantity 1 4517832 TOP COVER PAIN

Strona 51 - 13.7 Outdoor Unit: OU10-47T

APPENDIX A14-1SM SAFRPM 1-A.0 GBAPPENDIX AINSTALLATION AND OPERATION MANUAL► INSTALLATION & OPERATION MANUAL SAF024► INSTALLATION & OPERATI

Strona 52 - 13.8 Outdoor Unit: OU10-47T

PRODUCT DATA SHEET2-1SM SAFRPM 1-A.0 GB2. PRODUCT DATA SHEET2.1 SAF024 / OU7-24Z R410AModel Indoor Unit SAF024Model Outdoor Unit OU7-24ZInstallation

Strona 53 - 13.9 Outdoor Unit: GC 45 R22

PRODUCT DATA SHEET2-2SM SAFRPM 1-A.0 GB2.2 SAF045 / OU10-47T R410AModel Indoor Unit SAF045(FS)Model Outdoor Unit OU10-47T R410AInstallation method FL

Strona 54

PRODUCT DATA SHEET2-3SM SAFRPM 1-A.0 GB2.3 SAF045 / GC 45 R22Model Indoor Unit SAF045Model Outdoor Unit GC 45Installation Method of Pipe FlaredCharac

Strona 55 - APPENDIX A

3-1RATING CONDITIONS SM SAFRPM 1-A.0 GB3. RATING CONDITIONSStandard conditions in accordance with ISO 5151, ISO 13253