Electra OU10-47T ST Instrukcja Obsługi Strona 35

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 34
10-1
TUBING CONNECTIONS
SM SAFRPM 1-A.0 GB
10. TUBING CONNECTIONS
TUBE (Inch)
TORQUE (Nm)
¼” ”½”¾
Flare Nuts 11-13 40-45 60-65 70-75 80-85
Valve Cap 13-20 13-20 18-25 18-25 40-50
Service Port Cap 11-13 11-13 11-13 11-13 11-13
1. Valve Protection Cap-end
2. Refrigerant Valve Port (use Allen wrench to open/close)
3. Valve Protection Cap
4. Refrigerant Valve
5. Service Port Cap
6. Flare Nut
7. Unit Back Side
8. Copper Tube
When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along
the suction line at the lowest point of the riser. Incase the indoor unit is installed above the
outdoor, no trap is required.
CONTENTS
Przeglądanie stron 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 54 55

Komentarze do niniejszej Instrukcji

Brak uwag