PERFORMANCE DATA & PRESSURE CURVES
5-30 SM SX Ser1-A.3 GB
5.22.2 Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15 20 25
ENTERING AIR
WB OU COIL (°C)
TH PI TH PI TH PI
-10 4.79 2.10 4.61 2.24 4.43 2.35
-7 5.16 2.16 4.98 2.27 4.79 2.40
-2 5.48 2.18 5.30 2.31 5.11 2.45
2 6.66 2.29
6.39 2.43
6.12 2.58
6 8.55 2.46 8.30 2.63 8.01 2.79
10 9.30 2.60
9.05 2.77
8.80 2.97
15 10.04 2.71 9.79 2.92 9.55 3.10
20 10.58 2.79 10.33 3.02 10.04 3.26
* the above chart includes the weighted deicing infleuence.
LEGEND
TH – Total Heating Capacity, kW
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OU – Outdoor
5.23 Capacity Correction Factor Due to Tubing Length
5.23.1 Cooling
TOTAL TUBING LENGTH
4m
7.5m
10m 15m 20m 25m 30m 40m 50m
1.01
1
0.98 0.97 0.96 0.95 0.94 --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5.23.2 Heating
TOTAL TUBING LENGTH
4m
7.5m
10m 15m 20m 25m 30m 40m 50m
1.02
1
0.99 0.99 0.98 0.97 0.97 --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.